Plug and Socket (Auxiliary Accessories and Connection Components for Electrical Installations)
- Issuing authority
- OECD GlobalRecalls — KR
- Alert date
- 2025-07-17
- Country of alert
- Korea (Republic of)
What the authority reported
- Inadequate temperature rise (Measured) L-N test 67.9 K, (Standard) 45 K or below * Related standard: KC 60884-1, 19. Temperature rise - Noncompliance of terminals and permanently fixed terminals (Measured) No permanent connection (Standard) Non-replaceable connection devices should have permanent connections (terminations) such as soldering, welding, or equivalent permanent fixation. * Related standard: KC 60884-1, 12. Terminals and permanently fixed terminals - There is a risk of fire in case the temperature exceeds the standard. - Long-term use and aging may cause looseness at terminals, leading to short circuits and excessive temperature.
What to do
Follow the instructions in the official notice — recall remedies (refund, repair, replacement, or disposal) are defined by the issuing authority and the responsible business, and they differ per recall. Do not rely on summaries, including this one.
Record last checked against the registry on 2026-10-20.