Official recall record
Eterna semem3 self test emergency bulkhead
- Issuing authority
- OPSS (UK)
- Alert date
- 2023-11-30
- Country of alert
- United Kingdom
- Alert level
- Product Safety Report
- Alert type
- Product safety report
- Barcode (EAN/GTIN)
- 5013845058957
- Brand on record
- Eterna
What the authority reported
The product presents a risk of entrapment if following a power cut, the power is restored but then cuts out again disrupting the self-test setup sequence before it is completed (this takes approx. 5 seconds). The disruption of the self-test setup sequence may result in the fitting failing to default to emergency operation. This could mean that the product may not perform as expected when relied upon as guidance to safety. The product does not meet the requirements of the Electrical Equipment (Safety) Regulations 2016.
What to do
Follow the instructions in the official notice — recall remedies (refund, repair, replacement, or disposal) are defined by the issuing authority and the responsible business, and they differ per recall. Do not rely on summaries, including this one.
Record last checked against the registry on 2026-06-05.