Détecteur de fumée Alarmes incendie Alarmes de fumée à piles Installation facile

EU Safety Gate (RAPEX) · 2025-04-11 · FranceSerious risk
Issuing authority
EU Safety Gate (RAPEX)
Alert date
2025-04-11
Country of alert
France
Alert level
Serious risk
Risk type (official)
Asphyxiation, Fire

What the authority reported

The smoke detector fails to detect smoke coming from any direction and for each initial sensitivity. Moreover, the sound output is too low (measured values up to 59.9 dB(A)). Fire and/or smoke may develop without users being warned about it, creating a risk of asphyxiation and fire. The product does not comply with the Construction Products Regulation nor with the European standard EN 14604.